OBV5-B60 series Plug-in varistor-based lightning current arrester for 3-phase TN-S power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for Lightning Protection Levels III and IV, with remote indication contact. The combination lightning current and surge...
OBV5-B60 series
Plug-in varistor-based lightning current arrester for 3-phase TN-S power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for Lightning Protection Levels III and IV, with remote indication contact.
The combination lightning current and surge arrestors OBV5-B60 meet the type 1+2 requirement class according to IEC 61643-11. These devices protect low-voltage consumer systems from overvoltages of all types and are available in single-pole to four-pole versions. The use of high-performance varistors permits a rapid response time and a low protection level, without any line follow current. If circumstances are uncertain and there is a risk of fire from an overload, the internal cut-off unit disconnects the arrestor from the mains if necessary.
+ Connectable lightning current and surge arrestors
+ High arresting capacity up to 50 kA (10/350μs)
+ Visual status display
+ Available with optional remote signalling
+ Vibration-proof
+ Combination arrestors for buildings with lightning protection
+ Simple standard hat rail mounting
+ Labelled connections
+ Usable in systems with lightning protection class 3+4
Model: OBV5-B60 | |||
Maximum continuous voltage AC | Uc | V | 275/320/385/440 |
SPD to EN 61643-11 |
|
| Type 1+2 |
SPD to IEC 61643-1 |
|
| class I+II |
Lightning impulse current (10/350µs) | Iimp | kA | 12,5 |
Nominal discharge current (8/20µs) | In | kA | 30 |
Maximum discharge current (8/20µs) | Imax | kA | 60 |
Voltage protection level | Up | kV | < 1,5/1,8/2,0/2,2 |
Response time | tA | ns | < 25 |
Maximum back-up fuse |
| A | 125 |
Temperature range | ϑ | ℃ | -40℃~+85℃ |
Protection rating |
|
| IP 20 |
Max. cable cross-section flexible (fine-wire) |
| mm² | 25 |
Max. cable cross-section rigid (single wire/multi-wire) |
| mm² | 35 |
Welcome to buy the plug-in varistor-based lightning current arrester for 3-phase tn-s power supply networks with separate n and pe (5-conductor system: l1, l2, l3, n, pe), for lightning protection levels iii and iv, with remote indication contact with our professional manufacturers and suppliers. We are one of the famous brands and we are equipped with a productive factory at your service. Please be free to enjoy our good price and service.